Model
/ CAPACITY |
3
phase in 1 phase out |
3
phase in 3 phase out |
10KVA |
15KVA |
20KVA |
20KVA |
30KVA |
40KVA |
60KVA |
80KVA
|
| Input
Data |
|
| Nominal Voltage |
380Vac or 220Vac
adjustable at site |
380Vac |
| Input Voltage Range |
+/-25% |
| Frequency |
45-65Hz |
| Phase |
3 phase |
| Power Factor |
0.99 |
| Input Harmonics |
< / = 3% |
| Output Data |
|
| Voltage |
220Vac + / - 1% |
380Vac + / - 1% |
| Total Harmonics Distortion
|
Linear
load < 1%; non linear load < 2% |
| Frequency Synchronized With
Mains |
= / >
0.001% |
| Frequency Adjustable Range
|
50Hz
+/- 0.5 to +/- 2 adjustable |
| Overload Capability |
125%
15 min., 150% 1 min., >250% 200ms. |
| Crest Factor |
5:1 |
| Bypass Voltage Range |
from
+/-5% to +/-25% adjustable |
| Overall Efficiency |
96.5% |
| Charging |
intelligent
charging mode |
| Transfer Time |
zero |
| Dynamic Stability |
load
varying from 0 -100% or 100% - 0, output
voltage change < +/- 2% (recover to +/- 1% in 5ms. |
| Overload Capacity of Static
Bypass |
20 times
nominal current (100ms) |
| Display |
LCD+LED |
| Safety Standard |
CCEE
(EN60950) |
| Maximum Tolerable Voltage
|
6KV (transient) |
| EM Standard |
EN50091-2
class A |
| EMI Standard |
VDE0875 |
| MTBF (System) |
350,000
hrs. |
| Parallel Redundancy |
max.
8 units, modular parallel |
| Operating Condition |
|
| Working Temperature |
-5'C
to + 45'C |
| Storage Temperature |
-25'C
to 70'C |
| Continuous Working Temperature
|
max.
40'C for 8 hrs. |
| Relative Humidity |
0 - 95%
without condensation |
| Maximum Altitude |
3000M
above sea level (without derating) |
| Lightning Suppressor |
voltage
surge 10/700us current impulse 8/20us, 20kA |
| Insulation |
at 600V,
resistance > 2M ohm |
| Noise (1M) |
52dB |
| Protection Rating |
IP31 |
| Dimension (mm) W |
265 |
265 |
265 |
380 |
460 |
460 |
675 |
675 |
| Dimension (mm) H |
720 |
720 |
720 |
1050 |
1240 |
1240 |
1560 |
1560 |
| Dimension (mm) D |
580 |
580 |
580 |
700 |
790 |
790 |
840 |
840 |
| Weight (kg) |
40 |
55 |
60 |
80 |
130 |
135 |
280 |
290 |