Home
 
  Company Profile | Product | Features | Contact Us  
Product

Model / CAPACITY
DSP11-0010/1KVA
DSPL11-0010/1KVA
DSPB11-0020/2KVA
DSPB11-0020/2KVA
DSP11-0030/3KVA
DSPL11-0030/3KVA
DSP11-0060/6KVA
DSPL11-0060/6KVA
DSPB11-0100/10KVA
DSPL11-0100/10KVA
Input Data  
Nominal Voltage
220Vac
Voltage Range
160-276V : full load; 120-160V : linear derated; 120V 50% of full load.
176-276V : full load;
120-176 linear derated;
120V: 50% of full load.
Frequency
45-55Hz
Phase
single phase
Power Factor
0.99
Output Data  
Voltage
220+/-1% to 2% adjustable
Total Harmonics Distortion
linear load < 3%: non linear load < 5%
Frequency
When Mains at 50Hz +/-10%, follow Mains frequency; phase angle deviation less than 3 degree. When Mains is out of tolerance or when battery is discharging, frequency at 50Hz +/-0.2%
Inverter Overload Capability (Mains or Battery Mode)
105-125% : 15mins. 125-150% : 1min >150% : 200mS
Crest Factor
3:1
Bypass Voltage Range
120 - 253Vac
Overall Efficiency
>92%
Battery Data
Type (Standard)
sealed lead acid maintenance free battery. (12V/7Ah)
No. of Batteries
3
8
8
20
20
Nominal Voltage
36Vdc
96Vdc
96Vdc
240Vdc
240Vdc
Backup Time (Full Load)
> 8 mins.
> 10mins.
> 10mins.
> 10mins.
> 10mins.
Charging Time (Standard)
8 hrs.
Charging Current (Long Backup Model)
7A
6A
7A
Transfer Time
zero
Dynamic Stability
Load varying from 0-100% or 100%-0, output voltage change < +/-3%
Noise (1M)
<40dB
<45dB
48dB
Display
LED
LED + LCD (Chinese or English)
Safety Standard
CCEE (EN60950)
Maximum Tolerable Voltage
320Vac, 1hr. (static)
EM Standard
EN50091-2 Class B
Protection Rating
IEC 1000-4-2.3.4.5.11 Level III
EMI Rating
350,000 hrs.
MTBF (System)
reach IV installation requirement of IEC 60664-1, i.e. tolerate 1.2/50uS+8/20uS mixed capacity not lower than 6KV/3KV
Dimension
(W x D x H)mm
145 x 400x 220
192 x 460 x 350
260 x 570 x 720
Weight kg (Standard/Long Back Up Model)
14/8
40/20
45/21
94/50
178/80

 

Company Profile | Product | Features | Contact Us