Model
/ CAPACITY |
DSP11-0010/1KVA
DSPL11-0010/1KVA |
DSPB11-0020/2KVA
DSPB11-0020/2KVA |
DSP11-0030/3KVA
DSPL11-0030/3KVA |
DSP11-0060/6KVA
DSPL11-0060/6KVA |
DSPB11-0100/10KVA
DSPL11-0100/10KVA |
| Input
Data |
|
| Nominal Voltage |
220Vac |
| Voltage Range |
160-276V : full
load; 120-160V : linear derated; 120V 50% of full load.
|
176-276V : full load;
120-176 linear derated;
120V: 50% of full load. |
| Frequency |
45-55Hz |
| Phase |
single phase |
| Power Factor |
0.99 |
| Output
Data |
|
| Voltage |
220+/-1% to 2%
adjustable |
| Total Harmonics Distortion |
linear
load < 3%: non linear load < 5% |
| Frequency |
When
Mains at 50Hz +/-10%, follow Mains frequency; phase angle
deviation less than 3 degree. When Mains is out of tolerance
or when battery is discharging, frequency at 50Hz +/-0.2%
|
| Inverter Overload Capability (Mains
or Battery Mode) |
105-125%
: 15mins. 125-150% : 1min >150% : 200mS |
| Crest Factor |
3:1 |
| Bypass Voltage Range |
120 -
253Vac |
| Overall Efficiency |
>92% |
| Battery Data |
|
| Type (Standard) |
sealed
lead acid maintenance free battery. (12V/7Ah) |
| No. of Batteries |
3 |
8 |
8 |
20 |
20 |
| Nominal Voltage |
36Vdc |
96Vdc |
96Vdc |
240Vdc |
240Vdc |
| Backup Time (Full
Load) |
> 8 mins. |
> 10mins. |
> 10mins. |
> 10mins. |
> 10mins. |
| Charging Time (Standard)
|
8 hrs. |
| Charging Current
(Long Backup Model) |
7A |
6A |
7A |
| Transfer Time |
zero |
| Dynamic Stability
|
Load
varying from 0-100% or 100%-0, output voltage change <
+/-3% |
| Noise (1M) |
<40dB |
<45dB |
48dB |
| Display |
LED |
LED +
LCD (Chinese or English) |
| Safety Standard |
CCEE
(EN60950) |
| Maximum Tolerable
Voltage |
320Vac,
1hr. (static) |
| EM Standard |
EN50091-2
Class B |
| Protection Rating
|
IEC 1000-4-2.3.4.5.11
Level III |
| EMI Rating |
350,000
hrs. |
MTBF (System)
|
reach IV installation
requirement of IEC 60664-1, i.e. tolerate 1.2/50uS+8/20uS
mixed capacity not lower than 6KV/3KV |
Dimension
(W x D x H)mm |
145 x 400x 220 |
192 x 460 x 350 |
260 x 570 x 720 |
Weight kg
(Standard/Long Back Up Model) |
14/8 |
40/20 |
45/21 |
94/50 |
178/80 |